ASTM E119 versus a WUI wall test
ASTM E119 is a furnace fire-resistance method for building elements. Intertek’s public scope page says it measures how long an assembly contains a fire, keeps load, and limits heat, often followed by a hose stream. SFM 12-7A-1 is a 10-minute 150 kW flame on a siding and sheathing assembly. A 20-minute fire door is a different object. Do not swap them on a WUI wall.
You are looking at a wall section that says “1-hr Type X.” The sider thinks that is the wildfire path. The examiner wants the covering path in R327 or 12-7A-1. The furnace rating is still a party-wall or occupancy separation object.
No g3-passed exhibit matches this split. MECH-002 is the Steiner tunnel. MECH-003 is gypsum calcination. Do not reuse them as an E119 furnace.
Why it matters
People paste an interior fire-resistance hour onto an exterior WUI wall and call it done. Embers and a 10-minute flame against siding are not a furnace that heats the whole assembly from one side for an hour. The Type X path is a covering exception. It is not a shortcut to skip 12-7A-1 in California or to invent an hourly rating in Oregon.
How it works
E119, as labs describe it in public, puts a specimen on a furnace that follows a time-temperature curve. Failure is temperature rise, flames through, or load loss. Time is reported as 1/2-h, 1-h, 2-h. A hose stream may follow. That is structure fire from the inside of the building out, or occupancy separation.
WUI wall tests face flame or embers from outside. 12-7A-1 is ten minutes at 150 kW on the cladding and sheathing. ASTM E2707 is another exterior-wall flame method the site already carries. Neither is E119.
How the documents split
| Object | What it measures | What it is not |
|---|---|---|
| ASTM E119 (lab public scope) | Furnace duration, load, heat, hose stream | A WUI siding listing |
| SFM 12-7A-1 | 10 min, 150 kW, siding and sheathing | An hourly fire-resistance rating |
| Oregon Type X path | 5/8 in Type X behind the covering | “1 hour E119” on the elevation |
| 20-minute fire door | Interior-rated leaf | The exterior wall |
| Char rate | AWC βn from E119 furnace exposure | A deck or siding listing |
| Steiner tunnel | Surface flame spread | Fire-resistance hours |
The paths
1. Name the exposure. Interior fire-resistance is E119. Exterior wildfire flame on a wall is 12-7A-1 or E2707, or a deemed-to-comply covering path.
2. Do not relabel Type X as an hourly rating. Why Type X works is water in the core. The permit path is the covering exception. Hold the gypsum open until inspected.
3. Do not use a 20-minute door as the wall. WUI doors versus 20-minute fire doors.
4. California listing is still a model. 12-7A-1 is the test. The BML row is the listing. Listed is voluntary until the AHJ says otherwise.
5. Timber char is not siding. Char rate cites AWC’s E119-derived βn. Different object.
What people mix up
- E119 hours as a WUI wall pass.
- Type X chemistry as a 1-hour stamp on the elevation.
- 12-7A-1 as E84.
- A 20-minute fire door as the exterior wall.
- Hose-stream E119 as a wildfire hose attack.
How to check
- Read the test name on the drawing. E119, 12-7A-1, E2707, or Type X.
- Open the matching hub on this site. Confirm what it covers.
- If someone wrote “1-hr” on siding, ask which method. Furnace or wildfire flame.
- If the lot is Oregon R327, open the Type X path, not an E119 catalog.
- Do not download a paywalled E119 body from this page. Intertek is a lab description.
Limits
This page does not reprint the ASTM E119 time-temperature curve. The standard body was not opened. FireApproved is not ASTM and not OSFM. Use the method the adopted code names.
Related records
Questions
Is a 1-hour E119 wall a WUI wall?
Not by itself. E119 is a furnace method for how long an element contains fire and holds load. California’s SFM 12-7A-1 is a 10-minute 150 kW direct-flame exposure on a siding and sheathing assembly. Oregon’s Type X path is one layer of 5/8-inch Type X behind the covering. Those are different books.
Is the 20-minute fire door an E119 wall?
No. A 20-minute fire door is an interior-rated leaf. See WUI doors versus 20-minute fire doors. Do not specify a 20-minute door as the exterior wall assembly.
Does Type X chemistry equal an E119 rating?
No. Why Type X works is calcination. An E119 rating is an assembly in a furnace for a stated time. R327’s Type X path does not ask you to write “1 hour E119” on the siding.
Is char rate an E119 number?
AWC’s Fire Design Specification uses a nominal char rate from ASTM E119 furnace exposure. That is timber design, not a WUI siding listing. See char rate.
Sources
- 2025 California Wildland-Urban Interface Code construction notes, Section 504.5
- 2006 Utah Wildland-Urban Interface Code
- Salt Lake City Code 18.44.010 International Fire Code and Standards Adopted
- Taylorsville Ordinance 25-15 Utah Wildland Urban Interface Code
- ASTM E119 Standard Test Methods for Fire Tests of Building Construction and Materials
- SFM 12-7A-1
- 2023 ORSC Section R327 amendment
- 2025 Colorado Wildfire Resiliency Code