Home / Guides / How it works / ASTM E119 versus a WUI wall test

ASTM E119 versus a WUI wall test

Last verified 2026-08-27.

ASTM E119 is a furnace fire-resistance method for building elements. Intertek’s public scope page says it measures how long an assembly contains a fire, keeps load, and limits heat, often followed by a hose stream. SFM 12-7A-1 is a 10-minute 150 kW flame on a siding and sheathing assembly. A 20-minute fire door is a different object. Do not swap them on a WUI wall.

You are looking at a wall section that says “1-hr Type X.” The sider thinks that is the wildfire path. The examiner wants the covering path in R327 or 12-7A-1. The furnace rating is still a party-wall or occupancy separation object.

No g3-passed exhibit matches this split. MECH-002 is the Steiner tunnel. MECH-003 is gypsum calcination. Do not reuse them as an E119 furnace.

Why it matters

People paste an interior fire-resistance hour onto an exterior WUI wall and call it done. Embers and a 10-minute flame against siding are not a furnace that heats the whole assembly from one side for an hour. The Type X path is a covering exception. It is not a shortcut to skip 12-7A-1 in California or to invent an hourly rating in Oregon.

How it works

E119, as labs describe it in public, puts a specimen on a furnace that follows a time-temperature curve. Failure is temperature rise, flames through, or load loss. Time is reported as 1/2-h, 1-h, 2-h. A hose stream may follow. That is structure fire from the inside of the building out, or occupancy separation.

WUI wall tests face flame or embers from outside. 12-7A-1 is ten minutes at 150 kW on the cladding and sheathing. ASTM E2707 is another exterior-wall flame method the site already carries. Neither is E119.

How the documents split

ObjectWhat it measuresWhat it is not
ASTM E119 (lab public scope)Furnace duration, load, heat, hose streamA WUI siding listing
SFM 12-7A-110 min, 150 kW, siding and sheathingAn hourly fire-resistance rating
Oregon Type X path5/8 in Type X behind the covering“1 hour E119” on the elevation
20-minute fire doorInterior-rated leafThe exterior wall
Char rateAWC βn from E119 furnace exposureA deck or siding listing
Steiner tunnelSurface flame spreadFire-resistance hours

The paths

1. Name the exposure. Interior fire-resistance is E119. Exterior wildfire flame on a wall is 12-7A-1 or E2707, or a deemed-to-comply covering path.

2. Do not relabel Type X as an hourly rating. Why Type X works is water in the core. The permit path is the covering exception. Hold the gypsum open until inspected.

3. Do not use a 20-minute door as the wall. WUI doors versus 20-minute fire doors.

4. California listing is still a model. 12-7A-1 is the test. The BML row is the listing. Listed is voluntary until the AHJ says otherwise.

5. Timber char is not siding. Char rate cites AWC’s E119-derived βn. Different object.

What people mix up

  • E119 hours as a WUI wall pass.
  • Type X chemistry as a 1-hour stamp on the elevation.
  • 12-7A-1 as E84.
  • A 20-minute fire door as the exterior wall.
  • Hose-stream E119 as a wildfire hose attack.

How to check

  1. Read the test name on the drawing. E119, 12-7A-1, E2707, or Type X.
  2. Open the matching hub on this site. Confirm what it covers.
  3. If someone wrote “1-hr” on siding, ask which method. Furnace or wildfire flame.
  4. If the lot is Oregon R327, open the Type X path, not an E119 catalog.
  5. Do not download a paywalled E119 body from this page. Intertek is a lab description.

Limits

This page does not reprint the ASTM E119 time-temperature curve. The standard body was not opened. FireApproved is not ASTM and not OSFM. Use the method the adopted code names.

Questions

Is a 1-hour E119 wall a WUI wall?

Not by itself. E119 is a furnace method for how long an element contains fire and holds load. California’s SFM 12-7A-1 is a 10-minute 150 kW direct-flame exposure on a siding and sheathing assembly. Oregon’s Type X path is one layer of 5/8-inch Type X behind the covering. Those are different books.

Is the 20-minute fire door an E119 wall?

No. A 20-minute fire door is an interior-rated leaf. See WUI doors versus 20-minute fire doors. Do not specify a 20-minute door as the exterior wall assembly.

Does Type X chemistry equal an E119 rating?

No. Why Type X works is calcination. An E119 rating is an assembly in a furnace for a stated time. R327’s Type X path does not ask you to write “1 hour E119” on the siding.

Is char rate an E119 number?

AWC’s Fire Design Specification uses a nominal char rate from ASTM E119 furnace exposure. That is timber design, not a WUI siding listing. See char rate.