| Bark and wood mulch in the first five feet fail IBHS Essential Zone 0 IBHS Wildfire Prepared Home requires a 0–5 foot noncombustible zone. The technical standard requires removal of combustible groundcover, including wood and rubber mulch, to bare mineral soil. Bark, wood chips, and rubber mulch in that band fail Essential. | does not meet named test | 2026-08-23 | Voluntary program · ibhs-wildfire-prepared | IBHS + 1 |
| CAL FIRE puts the under-deck footprint in the ember-resistant zone CAL FIRE home-hardening guidance tells homeowners to keep the area beneath a deck and the first five feet around it clear of combustible material and to use hardscape in that zone. This is California mitigation guidance, not a construction-code application or an IBHS designation. | installation mistake | 2026-08-23 | California | CAL FIRE |
| Fascia and architectural trim boards are exempt from R327 eave-projection protection R327.3.4.1 requires protection of the exposed underside of rafter or truss eaves and enclosed soffits when any portion of the framing is under 12 feet. Exception 3 names fascia and other architectural trim boards. Wrapping fascia as if it were the eave assembly is not what that section requires. Confirm the drawing with the building official. | installation mistake | 2026-08-23 | Standard or listing system · orsc-r327 | Oregon Building Codes Division |
| Manufactured homes are outside Oregon R327 Oregon BCD’s local-adoption FAQ states Section R327 applies only to structures governed by the ORSC. Manufactured dwellings are factory-built to federal HUD standards and an Oregon installation code. They are not under ORSC scope. Deschutes County repeats that manufactured dwellings are not applicable. A wildfire package from a manufacturer is optional, not R327. | listing voluntary or absent | 2026-08-23 | Standard or listing system · orsc-r327 | Oregon Building Codes Division + 1 |
| Oregon guidance calls for noncombustible groundcover within five feet Oregon State Fire Marshal defensible-space guidance tells homeowners to use river rock, gravel, or pavers within five feet of the structure and to remove bark mulch from that buffer. This is statewide mitigation guidance, not an ORSC R327 application. | installation mistake | 2026-08-23 | Oregon | Oregon State Fire Marshal |
| Stairs to elevated decks have no R327 assembly requirement Deschutes County’s R327 page states R327 provides no code requirements for stair assemblies to elevated decks or landings, and that BCD treats those stairs as exempt. Walking-surface and underfloor rules for the deck are separate sentences. Do not copy the deck-board test onto the stair stringer without the official. | listing voluntary or absent | 2026-08-23 | Deschutes County | Deschutes County |
| Generic Trex is not the same as a named 8110 listing OSFM category 8110 lists named Trex Transcend models under listing IDs 8110-2052:0004, 8110-2052:0005, and 8110-2052:0501. Those rows are specific boards, thickness, edge, and gap. Writing “Trex” on a drawing is not those IDs. This finding does not say Trex is banned. Match the listing ID and the R327 walking-surface path. Confirm with the building official. | product line varies | 2026-08-23 | Standard or listing system · cal-fire-bml | CAL FIRE OSFM + 2 |
| Under-deck mesh belongs on the vertical plane to grade, not under the boards Screening laid horizontally under deck boards does not close the ember path from the side. The IBHS Wildfire Prepared Home standard calls for corrosion-resistant metal mesh to fully enclose the outer edge of the space beneath a deck down to the ground. | installation mistake | 2026-08-23 | Voluntary program · ibhs-wildfire-prepared | IBHS |
| Vented fiber-cement soffit is not by itself an ember-rated eave vent Perforated or louvered fiber-cement soffit panels are a cladding product. They are not a substitute for 1/16–1/8 inch noncombustible mesh or an ASTM E2886 listed vent where eave ventilation is allowed. Deschutes County’s R327 page flags soffits under 12 feet as a protected assembly. | not an ember rated vent | 2026-08-23 | Standard or listing system · astm-e2886 | Deschutes County + 1 |
| Wood shake and wood shingle roofs are not an R327 roof path Where Oregon R327 is adopted, roofing must be asphalt, slate, metal, tile, clay or concrete shingles, or other approved covering deemed equivalent to a minimum Class B roof assembly. Wood shingle and shake roofs are not permitted on structures in the designated area. | does not meet named test | 2026-08-23 | Standard or listing system · orsc-r327 | Oregon Building Codes Division |
| Coatings are not a listed R327 wall-covering path ORSC R327 lists noncombustible, ignition-resistant, heavy timber, log, or tested wall assemblies. Paint-on fire coatings are not in that list. Presenters at the 25 June 2026 Central Oregon Fire Hardening Codes Seminar stated coatings are not accepted to meet R327. Confirm with the local building official. | ahj does not accept | 2026-06-25 | Bend, Deschutes County | Oregon Building Codes Division + 1 |
| Foundation and underfloor vents may use mesh size. They are not required to be an ember-intrusion test. R327.3.2 allows underfloor ventilation openings to be covered with noncombustible corrosion-resistant metal wire mesh between 1/16 inch and 1/8 inch, or with vents designed to resist burning embers and flame, or other approved materials. Mesh is a sized screen, not ASTM E2886. Presenters at the 25 June 2026 Central Oregon seminar stated foundation vents need screen size, not an ember-intrusion test. Eave underside openings are a different sentence. | not an ember rated vent | 2026-06-25 | Bend, Deschutes County | Oregon Building Codes Division + 1 |
| Mechanical exhaust openings are not the R327.3.2 attic and underfloor vent rule R327.3.2 covers ventilation openings for enclosed attics, enclosed soffit spaces, enclosed rafter spaces, and underfloor spaces. It names mesh size or vents designed to resist burning embers and flame. It does not name bath fans, fireplaces, or fresh-air intakes. Presenters at the 25 June 2026 Central Oregon Fire Hardening Codes Seminar stated those mechanical openings sit outside that section. Confirm with the building official. | not an ember rated vent | 2026-06-25 | Bend, Deschutes County | Oregon Building Codes Division + 1 |