2024 IWUIC Class 1 and 2 Class A roof-assembly path
The unamended 2024 IWUIC model code specifies a Class A tested roof assembly for Class 1 and Class 2 ignition-resistant construction.
This is a model-code path, not a claim that IWUIC applies in any jurisdiction. A documented roof assembly can match the rating and test; deck, underlayment, profile-space, and local amendment review remain separate.
Published requirement text
“a Class A rating when tested in accordance with ASTM E108 or UL 790”
Where this instrument is documented
Set a location to read how this instrument lands where you are.
In Austin, this instrument has an active application record — 5 official checks open. Open the Austin record
In Clark County, this instrument has an active application record — 6 official checks open. Open the Clark County record
In Jackson, this instrument has an active application record — 5 official checks open. Open the Jackson record
In Prescott, this instrument has an active application record — 6 official checks open. Open the Prescott record
In Teton County, this instrument has an active application record — 6 official checks open. Open the Teton County record
In Washoe County, this instrument has an active application record — 6 official checks open. Open the Washoe County record
| Place | Force | Reach | Dated | Checks open | Source |
|---|---|---|---|---|---|
| Austin | active application documented | authority area | effective 2025-07-10 | 5 | Austin Ordinance 20250410-041 |
| Clark County | active application documented | unincorporated county | effective 2026-01-01 | 6 | Clark County Ordinance 5320 |
| Jackson | active application documented | incorporated boundary | effective 2025-01-01 | 5 | Town of Jackson Ordinance 1416 |
| Prescott | active application documented | incorporated boundary | adopted 2026-05-12 | 6 | Prescott City Code 6-2 Urban-Wildland Interface Code |
| Teton County | active application documented | unincorporated county | effective 2025-02-01 | 6 | 2024 Teton County Fire Code Resolution |
| Washoe County | active application documented | unincorporated county | effective 2025-07-01 | 6 | Washoe County Adopted Building Codes |
Machine-readable constraints
| Attribute | Operator | Value |
|---|---|---|
| assemblyRole | eq | roof-assembly |
| fireRating | eq | class-a |
| testStandard | in | astm-e108–ul-790 |
Products with documented matching attributes
| Product | Category | Status | Documented match evidence |
|---|---|---|---|
| Elastoflex SA P FR, Polyflex SA P FR, Elastobase V, Elastoflex SA V FR | roofing | Listed | |
| Owens Corning Titanium FR 0.032-inch aluminum-panel roof assembly | roofing | Attribute match | |
| Owens Corning Titanium FR 26-gauge steel-panel roof assembly | roofing | Attribute match | |
| Owens Corning Titanium FR asphalt-shingle roof assembly | roofing | Attribute match | |
| Owens Corning Titanium FR concrete-or-clay-tile roof assembly | roofing | Attribute match |