2018 IWUIC Class 2 Class B roof-assembly path

The unamended 2018 IWUIC specifies a Class B-or-better tested roof assembly for Class 2 ignition-resistant construction.

This is a model-code path, not a claim of local adoption. A documented roof assembly can match the minimum rating and test; the noncombustible-covering alternative, deck, underlayment, profile space, construction class, and local amendments remain separate checks.

code · Jurisdictions adopting unamended 2018 IWUIC Chapter 5 · Last verified 2026-08-26 · JSON (CC BY 4.0)

Published requirement text

“not less than a Class B rating when tested in accordance with ASTM E108 or UL 790”

2018 International Wildland-Urban Interface Code, Section 505.2 — International Code Council

Where this instrument is documented

Instrument iwuic-2018.

Set a location to read how this instrument lands where you are.

PlaceForceReachDatedChecks openSource
Eagle active application documented mapped area not sourced 6 Eagle City Code 7-1G-3 International Wildland-Urban Interface Code Adopted

Each place page carries that place's boundary, project scope and open official checks in full; this page's JSON twin carries them per application.

Machine-readable constraints

AttributeOperatorValue
assemblyRole eq roof-assembly
fireRating in class-a–class-b
testStandard in astm-e108–ul-790