Colorado CWRC roof-valley flashing metal path

The 2025 Colorado Wildfire Resiliency Code specifies No. 26 galvanized corrosion-resistant metal valley flashing over a full-width ASTM D3909 cap-sheet detail.

A flashing product can document the metal portion only. The 36-inch cap sheet, full-valley installation, compatibility, and locally adopted text remain separate checks.

code · Colorado jurisdictions adopting CWRC in mapped wildfire hazard areas · Last verified 2026-08-25 · JSON (CC BY 4.0)

Published requirement text

“not less than 0.019 inch (No. 26 galvanized sheet gage) corrosion-resistant metal”

2025 Colorado Wildfire Resiliency Code, Section 403.2.2 — Colorado Division of Fire Prevention and Control

Where this instrument is documented

Instrument cwrc-2025.

Set a location to read how this instrument lands where you are.

PlaceForceReachDatedChecks openSource
Colorado published for local adoption; not active statewide mapped area not sourced 4 2025 Colorado Wildfire Resiliency Code

Each place page carries that place's boundary, project scope and open official checks in full; this page's JSON twin carries them per application.

Machine-readable constraints

AttributeOperatorValueUnit
assemblyRole eq valley-flashing
sheetGauge lte 26 sheet-gauge
corrosionResistant eq true
material in galvanized-steel