Home / Requirements / Colorado CWRC wall-base protection

Colorado CWRC Class 2 wall-base protection path

The 2025 Colorado Wildfire Resiliency Code specifies a six-inch vertical metal or noncombustible detail between wall sheathing and cladding at ground, deck, and roof intersections.

A product can document role, height, and material only. Continuity, drainage, intersections, fastening, mapped class, and the adopted local detail remain project checks.

code · Colorado jurisdictions adopting CWRC in moderate or high mapped wildfire hazard areas · Last verified 2026-08-25 · JSON (CC BY 4.0)

Published requirement text

“A minimum of 6 inches of metal flashing or noncombustible material applied vertically”

2025 Colorado Wildfire Resiliency Code, Section 404.3.2 — Colorado Division of Fire Prevention and Control

Where this instrument is documented

Instrument cwrc-2025.

Set a location to read how this instrument lands where you are.

PlaceForceReachDatedChecks openSource
Colorado published for local adoption; not active statewide mapped area not sourced 4 2025 Colorado Wildfire Resiliency Code

Each place page carries that place's boundary, project scope and open official checks in full; this page's JSON twin carries them per application.