{"id":"iwuic-2024-roof-valley-flashing","license":"CC-BY-4.0","data":{"title":"2024 IWUIC roof-valley flashing metal path","shortName":"IWUIC valley flashing","summary":"The unamended 2024 IWUIC model code specifies No. 26 galvanized corrosion-resistant metal valley flashing over a named full-width cap-sheet detail.","framing":"A flashing product can document the metal portion only. The 36-inch cap sheet, full-valley installation, compatibility, and locally adopted text remain separate checks.","kind":"code","instrumentId":"iwuic-2024","jurisdiction":"Jurisdictions adopting unamended 2024 IWUIC Chapter 5","appliesToCategories":["roofing"],"quotedText":"not less than 0.019 inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal","source":{"title":"2024 International Wildland-Urban Interface Code, Sections 504.2.1, 505.2.1, and 506.2.1","url":"https://codes.iccsafe.org/content/IWUIC2024P1/chapter-5-special-building-construction-regulations","publisher":"International Code Council","sourceType":"official","accessedOn":"2026-08-25T00:00:00.000Z","documentDate":"2023-08-01T00:00:00.000Z"},"constraints":[{"attribute":"assemblyRole","op":"eq","value":"valley-flashing"},{"attribute":"sheetGauge","op":"lte","value":26,"unit":"sheet-gauge"},{"attribute":"corrosionResistant","op":"eq","value":true},{"attribute":"material","op":"in","value":["galvanized-steel"]}],"relatedStandards":["iwuic"],"author":"grayson-graham","reviewStatus":"draft","lastVerified":"2026-08-25T00:00:00.000Z"},"applications":[{"id":"iwuic-2024-austin","title":"Austin 2024 IWUIC proximity-zone application","instrumentId":"iwuic-2024","placeId":"us-tx-austin","status":"active","geographicScope":"authority-area","scopeSummary":"Austin applies its amended 2024 IWUIC to submissions on or after July 10, 2025 in City full-purpose and limited-purpose areas, subject to transition, official WUI, proximity-zone, project, and mixed-jurisdiction determinations.","adoptedOn":"2025-04-10T00:00:00.000Z","effectiveOn":"2025-07-10T00:00:00.000Z","requirementIds":["iwuic-2024-class-1-2-class-a-roof-assembly","iwuic-2024-class-1-2-noncombustible-exterior-wall","iwuic-2024-class-1-wall-base-protection","iwuic-2024-roof-profile-closure","iwuic-2024-roof-valley-flashing","iwuic-2024-vent-mesh","iwuic-2024-noncombustible-gutters","iwuic-2024-austin-zone-a-20-minute-exterior-door","iwuic-2024-austin-zone-a-noncombustible-exterior-door","iwuic-2024-austin-zone-a-solid-core-exterior-door","iwuic-2024-austin-zone-a-multilayered-glazing","iwuic-2024-austin-zones-b-c-multilayered-skylight","iwuic-2024-austin-zone-a-noncombustible-appendage","iwuic-2024-austin-zone-b-30-foot-noncombustible-appendage","iwuic-2024-austin-zone-c-10-foot-noncombustible-appendage","iwuic-2024-austin-zone-a-noncombustible-eave","iwuic-2024-austin-zones-b-c-noncombustible-eave","iwuic-2024-austin-zones-b-c-solid-eave-enclosure","iwuic-2024-austin-zone-c-class-a-roof-assembly","iwuic-2024-austin-zones-a-b-c-gutter-noncorrosive-material"],"requirementCoverage":"complete","requirementCoverageSummary":"All 15 normalized model material rows were reviewed against the enacted Austin amendments; this is complete only for that model crosswalk, not full-code normalization or a finding that every row applies to one project.","requirementScopes":[{"requirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","scopeKeys":["proximity-zone-a","proximity-zone-b"],"scopeSummary":"The unchanged Class A roof atom is joined only for Austin Proximity Zones A and B.","sourceSections":["504.2","505.2"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","scopeKeys":["proximity-zone-a","proximity-zone-b"],"scopeSummary":"The unchanged noncombustible exterior-wall path is joined only for Austin Proximity Zones A and B.","sourceSections":["504.5","505.5"]},{"requirementId":"iwuic-2024-class-1-wall-base-protection","scopeKeys":["proximity-zone-a"],"scopeSummary":"The unchanged six-inch wall-base path is joined only for Austin Proximity Zone A.","sourceSections":["504.5.1"]},{"requirementId":"iwuic-2024-roof-profile-closure","scopeKeys":["proximity-zone-a","proximity-zone-b","proximity-zone-c"],"scopeSummary":"The roof-profile closure atom is retained across Austin Proximity Zones A, B, and C.","sourceSections":["504.2","505.2","506.2"]},{"requirementId":"iwuic-2024-roof-valley-flashing","scopeKeys":["proximity-zone-a","proximity-zone-b","proximity-zone-c"],"scopeSummary":"The metal valley-flashing atom is retained across all zones, with local woven-valley alternatives remaining separate.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"requirementId":"iwuic-2024-vent-mesh","scopeKeys":["proximity-zone-a","proximity-zone-b","proximity-zone-c"],"scopeSummary":"The one-eighth-inch mesh path remains available across all zones; Zone C also has a listed-vent alternative.","sourceSections":["504.10.2","505.10.2","506.5.1","506.5.2"]},{"requirementId":"iwuic-2024-austin-zone-a-20-minute-exterior-door","scopeKeys":["proximity-zone-a"],"scopeSummary":"The 20-minute exterior-door path survives in Zone A only because Austin deletes Section 505.9.","sourceSections":["504.9","25-12-181(B)"]},{"requirementId":"iwuic-2024-austin-zone-a-noncombustible-exterior-door","scopeKeys":["proximity-zone-a"],"scopeSummary":"The noncombustible exterior-door path survives in Zone A only because Austin deletes Section 505.9.","sourceSections":["504.9","25-12-181(B)"]},{"requirementId":"iwuic-2024-austin-zone-a-solid-core-exterior-door","scopeKeys":["proximity-zone-a"],"scopeSummary":"The solid-core exterior-door path survives in Zone A only because Austin deletes Section 505.9.","sourceSections":["504.9","25-12-181(B)"]},{"requirementId":"iwuic-2024-austin-zone-a-multilayered-glazing","scopeKeys":["proximity-zone-a"],"scopeSummary":"Zone A retains the broad exterior-opening multilayered-glazing path in Section 504.8.","sourceSections":["504.8"]},{"requirementId":"iwuic-2024-austin-zones-b-c-multilayered-skylight","scopeKeys":["proximity-zone-b","proximity-zone-c"],"scopeSummary":"Austin's rewritten Zones B and C glazing text limits this multilayered path to skylights.","sourceSections":["505.8","506.7"]},{"requirementId":"iwuic-2024-austin-zone-a-noncombustible-appendage","scopeKeys":["proximity-zone-a"],"scopeSummary":"Zone A covers attached appendages and detached unenclosed accessory structures without a distance predicate.","sourceSections":["504.7"]},{"requirementId":"iwuic-2024-austin-zone-b-30-foot-noncombustible-appendage","scopeKeys":["proximity-zone-b","within-30-feet-of-habitable-space"],"scopeSummary":"Zone B reaches an unenclosed appendage or structure attached to or within 30 feet of habitable space.","sourceSections":["505.7"]},{"requirementId":"iwuic-2024-austin-zone-c-10-foot-noncombustible-appendage","scopeKeys":["proximity-zone-c","within-10-feet-of-habitable-space"],"scopeSummary":"Zone C reaches an unenclosed appendage or structure attached to or within 10 feet of habitable space.","sourceSections":["506.6"]},{"requirementId":"iwuic-2024-austin-zone-a-noncombustible-eave","scopeKeys":["proximity-zone-a"],"scopeSummary":"Austin Zone A retains the noncombustible ignition-resistant eave path through Sections 503.2.1 and 504.3.1.","sourceSections":["503.2.1","504.3.1"]},{"requirementId":"iwuic-2024-austin-zones-b-c-noncombustible-eave","scopeKeys":["proximity-zone-b","proximity-zone-c"],"scopeSummary":"Austin expressly permits the noncombustible enclosed-eave path in Zones B and C.","sourceSections":["505.3.1","506.4.1"]},{"requirementId":"iwuic-2024-austin-zones-b-c-solid-eave-enclosure","scopeKeys":["proximity-zone-b","proximity-zone-c"],"scopeSummary":"The three-quarter-inch solid eave-enclosure path is joined only for Austin Zones B and C.","sourceSections":["505.3.1","506.4.1"]},{"requirementId":"iwuic-2024-austin-zone-c-class-a-roof-assembly","scopeKeys":["proximity-zone-c"],"scopeSummary":"Austin replaces the model Class 3 Class B minimum with a Class A roof assembly in Zone C.","sourceSections":["506.2"]},{"requirementId":"iwuic-2024-noncombustible-gutters","scopeKeys":["proximity-zone-a","proximity-zone-b","proximity-zone-c"],"scopeSummary":"The unchanged model noncombustible gutter-and-downspout atom applies in every Austin proximity zone.","sourceSections":["504.4","505.4","506.4.6"]},{"requirementId":"iwuic-2024-austin-zones-a-b-c-gutter-noncorrosive-material","scopeKeys":["proximity-zone-a","proximity-zone-b","proximity-zone-c"],"scopeSummary":"Austin's added noncorrosive-material condition applies to gutters—not downspouts—in every zone; the approved debris-control means remains an assembly and official check.","sourceSections":["504.4","505.4","506.4.6"]}],"requirementCrosswalk":[{"modelRequirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","disposition":"locally-modified","replacementRequirementIds":["iwuic-2024-austin-zone-a-20-minute-exterior-door"],"scopeSummary":"Section 504.9 survives for Zone A, but Austin deletes Section 505.9, so the combined model row is replaced.","sourceSections":["504.9","505.9","25-12-181(B)"]},{"modelRequirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The model Class A roof atom remains unchanged for Austin Zones A and B.","sourceSections":["504.2","505.2"]},{"modelRequirementId":"iwuic-2024-class-1-2-multilayered-glazing","disposition":"locally-modified","replacementRequirementIds":["iwuic-2024-austin-zone-a-multilayered-glazing","iwuic-2024-austin-zones-b-c-multilayered-skylight"],"scopeSummary":"Zone A retains the broad path, while rewritten Zones B and C restrict the path to skylights.","sourceSections":["504.8","505.8","506.7"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-deck","disposition":"locally-modified","replacementRequirementIds":["iwuic-2024-austin-zone-a-noncombustible-appendage","iwuic-2024-austin-zone-b-30-foot-noncombustible-appendage","iwuic-2024-austin-zone-c-10-foot-noncombustible-appendage"],"scopeSummary":"Austin rewrites appendage reach separately for Zone A, Zone B within 30 feet, and Zone C within 10 feet.","sourceSections":["504.7","505.7","506.6"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","disposition":"locally-modified","replacementRequirementIds":["iwuic-2024-austin-zone-a-noncombustible-exterior-door"],"scopeSummary":"Section 504.9 survives for Zone A, but Austin deletes Section 505.9, so the combined model row is replaced.","sourceSections":["504.9","505.9","25-12-181(B)"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The model noncombustible exterior-wall atom remains unchanged for Austin Zones A and B.","sourceSections":["504.5","505.5"]},{"modelRequirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","disposition":"locally-modified","replacementRequirementIds":["iwuic-2024-austin-zone-a-solid-core-exterior-door"],"scopeSummary":"Section 504.9 survives for Zone A, but Austin deletes Section 505.9, so the combined model row is replaced.","sourceSections":["504.9","505.9","25-12-181(B)"]},{"modelRequirementId":"iwuic-2024-class-1-noncombustible-eave","disposition":"locally-modified","replacementRequirementIds":["iwuic-2024-austin-zone-a-noncombustible-eave","iwuic-2024-austin-zones-b-c-noncombustible-eave"],"scopeSummary":"Austin rewrites eave construction by proximity zone; the noncombustible path is normalized separately for Zone A and Zones B/C.","sourceSections":["504.3","504.3.1","505.3.1","506.4.1"]},{"modelRequirementId":"iwuic-2024-class-1-wall-base-protection","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The model wall-base protection atom remains unchanged for Austin Zone A.","sourceSections":["504.5.1"]},{"modelRequirementId":"iwuic-2024-class-2-solid-eave-enclosure","disposition":"locally-modified","replacementRequirementIds":["iwuic-2024-austin-zones-b-c-solid-eave-enclosure"],"scopeSummary":"Austin rewrites Zone B eaves and adds matching Zone C text, so the model row is replaced with local scope.","sourceSections":["505.3","505.3.1","506.4.1"]},{"modelRequirementId":"iwuic-2024-class-3-class-b-roof-assembly","disposition":"deleted-and-replaced","replacementRequirementIds":["iwuic-2024-austin-zone-c-class-a-roof-assembly"],"scopeSummary":"Austin rewrites Section 506.2 to require Class A in Zone C instead of the model Class B minimum.","sourceSections":["506.2"]},{"modelRequirementId":"iwuic-2024-noncombustible-gutters","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Austin retains the model noncombustible gutter-and-downspout sentence in all three zones, then adds a separate gutter-only condition.","sourceSections":["504.4","505.4","506.4.6"]},{"modelRequirementId":"iwuic-2024-roof-profile-closure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The profile-space closure atom is retained in Zones A and B and repeated in rewritten Zone C Section 506.2.","sourceSections":["504.2","505.2","506.2"]},{"modelRequirementId":"iwuic-2024-roof-valley-flashing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The model metal valley-flashing atom remains, with local woven-valley alternatives layered alongside it.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"modelRequirementId":"iwuic-2024-vent-mesh","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The prescriptive mesh atom remains in every zone; Zone C additionally offers a listed-vent path.","sourceSections":["504.10.2","505.10.2","506.5.1","506.5.2"]}],"map":{"status":"linked-official-tool","summary":"Austin's official map is a starting point; onsite measurement and the code official determine WUI and proximity-zone results.","url":"https://austin.maps.arcgis.com/apps/instant/media/index.html?appid=0c0889a8bac34cf4a1ca6ce6777c3937","source":{"title":"Austin WUI Code map","url":"https://austin.maps.arcgis.com/apps/instant/media/index.html?appid=0c0889a8bac34cf4a1ca6ce6777c3937","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},"projectTriggers":[{"summary":"Chapter 5 reaches a building or structure constructed, modified, located in, or relocated into a designated WUI area.","sourceSections":["503.1"],"source":{"title":"Austin Ordinance 20250410-041","url":"https://services.austintexas.gov/edims/document.cfm?id=451971","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-04-10T00:00:00.000Z"}},{"summary":"Austin Fire describes full-purpose and limited-purpose City areas as in scope, fully ETJ parcels as out, and mixed jurisdictions as case-by-case.","sourceSections":["Current administrative scope"],"source":{"title":"Wildland-Urban Interface Code","url":"https://www.austintexas.gov/fire/wildland-urban-interface-code","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"Austin Fire assigns submissions from January 1, 2021 through July 9, 2025 to the amended 2015 IWUIC and submissions on or after July 10, 2025 to the amended 2024 IWUIC.","sourceSections":["Austin WUI Code History"],"source":{"title":"Wildland-Urban Interface Code","url":"https://www.austintexas.gov/fire/wildland-urban-interface-code","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}}],"localAmendments":[{"kind":"transition","section":"Austin WUI Code History","summary":"Application submissions from January 1, 2021 through July 9, 2025 use the amended 2015 IWUIC; submissions on or after July 10, 2025 use the amended 2024 IWUIC.","source":{"title":"Wildland-Urban Interface Code","url":"https://www.austintexas.gov/fire/wildland-urban-interface-code","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"kind":"transition","section":"Changes to Approved Site Plans","summary":"Site plans approved under the 2015 IWUIC or earlier retain the older-code treatment for the vicinity plan, individual-structure access and water supply, access, defensible space, and ember ignition zone; a modification adding a structure or unit or increasing fire area must meet the updated rules for the revised portion, and permits submitted on or after July 10, 2025 use the 2024 IWUIC.","source":{"title":"Wildland-Urban Interface Code","url":"https://www.austintexas.gov/fire/wildland-urban-interface-code","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"kind":"transition","section":"WUI Vicinity Plans","summary":"A WUI Vicinity Plan approved under the 2015 IWUIC may be used for new phases in the same subdivision unless changes affect structure-to-wildland proximity; a PUD plan covering only part of the project does not cover other sections unless the approved PUD agreement does.","source":{"title":"Wildland-Urban Interface Code","url":"https://www.austintexas.gov/fire/wildland-urban-interface-code","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"kind":"transition","section":"Volume Builder Program Participants","summary":"Master Plans submitted before July 10, 2025 may continue with the 2021 Residential Code and 2015 IWUIC for that section or phase; new sections or phases needing a new Master Plan and Master Plans submitted on or after that date use the 2024 technical codes, and older prototypes require updating before reuse.","source":{"title":"Wildland-Urban Interface Code","url":"https://www.austintexas.gov/fire/wildland-urban-interface-code","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"kind":"deletion","section":"25-12-181(E)","summary":"Austin deletes the model Class 1, Class 2, and Class 3 ignition-resistant-construction definitions.","source":{"title":"Austin Ordinance 20250410-041","url":"https://services.austintexas.gov/edims/document.cfm?id=451971","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-04-10T00:00:00.000Z"}},{"kind":"modification","section":"503.1 and 504–506","summary":"Austin substitutes Proximity Zones A, B, and C for the model construction classes and rewrites affected material scopes.","source":{"title":"Austin Ordinance 20250410-041","url":"https://services.austintexas.gov/edims/document.cfm?id=451971","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-04-10T00:00:00.000Z"}},{"kind":"deletion","section":"505.9","summary":"Austin deletes the model Zone B exterior-door section, so the combined Class 1 and 2 door rows cannot remain joined.","source":{"title":"Austin Ordinance 20250410-041","url":"https://services.austintexas.gov/edims/document.cfm?id=451971","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-04-10T00:00:00.000Z"}}],"supportingSources":[{"title":"Wildland-Urban Interface Code","url":"https://www.austintexas.gov/fire/wildland-urban-interface-code","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}],"unresolvedPredicates":["official-boundary","official-hazard-map","project-type","effective-date","official-confirmation"],"source":{"title":"Austin Ordinance 20250410-041","url":"https://services.austintexas.gov/edims/document.cfm?id=451971","publisher":"City of Austin","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-04-10T00:00:00.000Z"},"author":"grayson-graham","reviewStatus":"draft","lastVerified":"2026-08-26T00:00:00.000Z"},{"id":"iwuic-2024-clark-county","title":"Clark County 2024 IWUIC application","instrumentId":"iwuic-2024","placeId":"us-nv-clark","status":"active","geographicScope":"unincorporated-county","scopeSummary":"Clark County applies its 2024 IWUIC through the County Fire Department's unincorporated service jurisdiction; official boundary, WUI map, assigned IR class, project, and code-official checks remain open.","adoptedOn":"2025-12-02T00:00:00.000Z","effectiveOn":"2026-01-01T00:00:00.000Z","requirementIds":["iwuic-2024-class-1-2-20-minute-exterior-door","iwuic-2024-class-1-2-class-a-roof-assembly","iwuic-2024-class-1-2-multilayered-glazing","iwuic-2024-class-1-2-noncombustible-deck","iwuic-2024-class-1-2-noncombustible-exterior-door","iwuic-2024-class-1-2-noncombustible-exterior-wall","iwuic-2024-class-1-2-solid-core-exterior-door","iwuic-2024-class-1-noncombustible-eave","iwuic-2024-class-1-wall-base-protection","iwuic-2024-class-2-solid-eave-enclosure","iwuic-2024-class-3-class-b-roof-assembly","iwuic-2024-noncombustible-gutters","iwuic-2024-roof-profile-closure","iwuic-2024-roof-valley-flashing","iwuic-2024-vent-mesh"],"requirementCoverage":"complete","requirementCoverageSummary":"All 15 normalized model material rows were reviewed against Ordinance 5320; this is complete only for that model crosswalk, not full-code normalization or a finding that every class row applies to one project.","requirementScopes":[{"requirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This exterior-door path applies only when the County assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This Class A roof path applies only when the County assigns IR1 or IR2 construction.","sourceSections":["504.2","505.2"]},{"requirementId":"iwuic-2024-class-1-2-multilayered-glazing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This multilayered-glazing path applies only when the County assigns IR1 or IR2 construction.","sourceSections":["504.8","505.8"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-deck","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible appendage path applies only when the County assigns IR1 or IR2 construction.","sourceSections":["504.7","505.7"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-door path applies only when the County assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-wall path applies only when the County assigns IR1 or IR2 construction.","sourceSections":["504.5","505.5"]},{"requirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This solid-core exterior-door path applies only when the County assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-noncombustible-eave","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This eave path applies only when the County assigns IR1 construction.","sourceSections":["503.2.1","504.3"]},{"requirementId":"iwuic-2024-class-1-wall-base-protection","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This wall-base path applies only when the County assigns IR1 construction.","sourceSections":["504.5.1"]},{"requirementId":"iwuic-2024-class-2-solid-eave-enclosure","scopeKeys":["ignition-resistant-class-2"],"scopeSummary":"This solid eave-enclosure path applies only when the County assigns IR2 construction.","sourceSections":["505.3"]},{"requirementId":"iwuic-2024-class-3-class-b-roof-assembly","scopeKeys":["ignition-resistant-class-3"],"scopeSummary":"This Class B roof path applies only when the County assigns IR3 construction.","sourceSections":["506.2"]},{"requirementId":"iwuic-2024-noncombustible-gutters","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This gutter-and-downspout path applies after the County assigns IR1, IR2, or IR3 construction.","sourceSections":["504.4","505.4","506.4"]},{"requirementId":"iwuic-2024-roof-profile-closure","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This roof-profile closure applies after the County assigns IR1, IR2, or IR3 construction.","sourceSections":["504.2","505.2","506.2"]},{"requirementId":"iwuic-2024-roof-valley-flashing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This valley-flashing path applies after the County assigns IR1, IR2, or IR3 construction.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"requirementId":"iwuic-2024-vent-mesh","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This vent-mesh path applies after the County assigns IR1, IR2, or IR3 construction.","sourceSections":["504.10.2","505.10.2","506.5"]}],"requirementCrosswalk":[{"modelRequirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 exterior-door atom.","sourceSections":["13.08.060","504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 Class A roof atom.","sourceSections":["13.08.060","504.2","505.2"]},{"modelRequirementId":"iwuic-2024-class-1-2-multilayered-glazing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 multilayered-glazing atom.","sourceSections":["13.08.060","504.8","505.8"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-deck","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 noncombustible-appendage atom.","sourceSections":["13.08.060","504.7","505.7"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 noncombustible-door atom.","sourceSections":["13.08.060","504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 noncombustible-wall atom.","sourceSections":["13.08.060","504.5","505.5"]},{"modelRequirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 solid-core-door atom.","sourceSections":["13.08.060","504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-noncombustible-eave","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 noncombustible-eave atom.","sourceSections":["13.08.060","503.2.1","504.3"]},{"modelRequirementId":"iwuic-2024-class-1-wall-base-protection","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 wall-base atom.","sourceSections":["13.08.060","504.5.1"]},{"modelRequirementId":"iwuic-2024-class-2-solid-eave-enclosure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 solid-eave atom.","sourceSections":["13.08.060","505.3"]},{"modelRequirementId":"iwuic-2024-class-3-class-b-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 Class B roof atom.","sourceSections":["13.08.060","506.2"]},{"modelRequirementId":"iwuic-2024-noncombustible-gutters","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 noncombustible-gutter atom.","sourceSections":["13.08.060","504.4","505.4","506.4"]},{"modelRequirementId":"iwuic-2024-roof-profile-closure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 roof-profile atom.","sourceSections":["13.08.060","504.2","505.2","506.2"]},{"modelRequirementId":"iwuic-2024-roof-valley-flashing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 valley-flashing atom.","sourceSections":["13.08.060","504.2.1","505.2.1","506.2.1"]},{"modelRequirementId":"iwuic-2024-vent-mesh","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Clark's enumerated amendments do not modify the Chapter 5 prescriptive vent-mesh atom.","sourceSections":["13.08.060","504.10.2","505.10.2","506.5"]}],"map":{"status":"official-map-required-not-located","summary":"Ordinance 5320 requires public or electronic WUI mapping unless the community risk assessment identifies no WUI; no current official map URL or project-specific IR-class answer was located.","source":{"title":"Clark County Ordinance 5320, Section 13.08.080","url":"https://weddings.vegas/wp-content/uploads/2026/02/ORD-5320.pdf","publisher":"Clark County, Nevada","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-12-02T00:00:00.000Z"}},"projectTriggers":[{"summary":"The adopted model code reaches only officially declared WUI areas, and Clark's ordinance requires the code official to review those areas.","sourceSections":["302.1","302.2","302.3"],"source":{"title":"Clark County Ordinance 5320","url":"https://weddings.vegas/wp-content/uploads/2026/02/ORD-5320.pdf","publisher":"Clark County, Nevada","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-12-02T00:00:00.000Z"}}],"localAmendments":[{"kind":"modification","section":"13.08.070–13.08.085","summary":"Ordinance 5320 enumerates local changes in Chapters 1, 3, and 4; it does not enumerate a Chapter 5 amendment.","source":{"title":"Clark County Ordinance 5320","url":"https://weddings.vegas/wp-content/uploads/2026/02/ORD-5320.pdf","publisher":"Clark County, Nevada","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-12-02T00:00:00.000Z"}},{"kind":"modification","section":"302.2","summary":"Clark requires public or electronic WUI mapping unless its community risk assessment identifies no WUI areas.","source":{"title":"Clark County Ordinance 5320","url":"https://weddings.vegas/wp-content/uploads/2026/02/ORD-5320.pdf","publisher":"Clark County, Nevada","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-12-02T00:00:00.000Z"}}],"supportingSources":[{"title":"Clark County Code and ordinances","url":"https://www.clarkcountynv.gov/government/elected_officials/county_clerk/county-code","publisher":"Clark County, Nevada","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"},{"title":"Clark County jurisdiction locator","url":"https://www.clarkcountynv.gov/business/doing_business_with_clark_county/divisions/sports_and_special_events/clark-county-jurisdiction-locator","publisher":"Clark County, Nevada","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}],"unresolvedPredicates":["official-boundary","official-hazard-map","official-hazard-class","project-type","effective-date","official-confirmation"],"source":{"title":"Clark County Ordinance 5320","url":"https://weddings.vegas/wp-content/uploads/2026/02/ORD-5320.pdf","publisher":"Clark County, Nevada","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-12-02T00:00:00.000Z"},"author":"grayson-graham","reviewStatus":"draft","lastVerified":"2026-08-26T00:00:00.000Z"},{"id":"iwuic-2024-prescott","title":"Prescott 2024 IWUIC application","instrumentId":"iwuic-2024","placeId":"us-az-prescott","status":"active","geographicScope":"incorporated-boundary","scopeSummary":"Prescott declares its entire incorporated city boundary a WUI, applies its amended 2024 IWUIC there, and uses City predictive modeling and GIS to assign extreme/IR1, high/IR2, or moderate/IR3 construction; boundary, project, risk-class, effective-date, and official checks remain open.","adoptedOn":"2026-05-12T00:00:00.000Z","requirementIds":["iwuic-2024-class-1-2-20-minute-exterior-door","iwuic-2024-class-1-2-class-a-roof-assembly","iwuic-2024-class-1-2-multilayered-glazing","iwuic-2024-class-1-2-noncombustible-deck","iwuic-2024-class-1-2-noncombustible-exterior-door","iwuic-2024-class-1-2-noncombustible-exterior-wall","iwuic-2024-class-1-2-solid-core-exterior-door","iwuic-2024-class-1-noncombustible-eave","iwuic-2024-class-1-wall-base-protection","iwuic-2024-class-2-solid-eave-enclosure","iwuic-2024-noncombustible-gutters","iwuic-2024-roof-profile-closure","iwuic-2024-roof-valley-flashing","iwuic-2024-vent-mesh","iwuic-2024-prescott-class-3-class-a-roof-assembly","iwuic-2024-prescott-class-3-one-hour-eave"],"requirementCoverage":"complete","requirementCoverageSummary":"All 15 normalized 2024 model material rows were reviewed against Prescott's enumerated amendments; the model Class 3 Class B roof row is replaced, and one source-explicit local eave path is added. This is not full-code normalization, does not normalize ignition-resistant or dimensional-lumber alternatives that lack exact product-field semantics, and does not establish which class applies to one project.","requirementScopes":[{"requirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This exterior-door path applies only after the City assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This Class A roof path applies only after the City assigns IR1 or IR2 construction.","sourceSections":["504.2","505.2"]},{"requirementId":"iwuic-2024-class-1-2-multilayered-glazing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This multilayered-glazing path applies only after the City assigns IR1 or IR2 construction.","sourceSections":["504.8","505.8"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-deck","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible appendage path applies only after the City assigns IR1 or IR2 construction.","sourceSections":["504.7","505.7"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-door path applies only after the City assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-wall path applies only after the City assigns IR1 or IR2 construction.","sourceSections":["504.5","505.5"]},{"requirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This solid-core exterior-door path applies only after the City assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-noncombustible-eave","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This noncombustible eave path applies only after the City assigns IR1 construction.","sourceSections":["503.2.1","504.3"]},{"requirementId":"iwuic-2024-class-1-wall-base-protection","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This wall-base path applies only after the City assigns IR1 construction.","sourceSections":["504.5.1"]},{"requirementId":"iwuic-2024-class-2-solid-eave-enclosure","scopeKeys":["ignition-resistant-class-2"],"scopeSummary":"This solid eave-enclosure path applies only after the City assigns IR2 construction.","sourceSections":["505.3"]},{"requirementId":"iwuic-2024-noncombustible-gutters","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This gutter-and-downspout path applies after the City assigns IR1, IR2, or IR3 construction.","sourceSections":["504.4","505.4","506.4"]},{"requirementId":"iwuic-2024-roof-profile-closure","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This roof-profile closure applies after the City assigns IR1, IR2, or IR3 construction.","sourceSections":["504.2","505.2","506.2"]},{"requirementId":"iwuic-2024-roof-valley-flashing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This valley-flashing path applies after the City assigns IR1, IR2, or IR3 construction.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"requirementId":"iwuic-2024-vent-mesh","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This prescriptive vent path applies after the City assigns IR1, IR2, or IR3 construction.","sourceSections":["504.10.2","505.10.2","506.5"]},{"requirementId":"iwuic-2024-prescott-class-3-class-a-roof-assembly","scopeKeys":["ignition-resistant-class-3"],"scopeSummary":"Prescott's local Class A replacement applies only after the City assigns IR3 construction.","sourceSections":["506.2"]},{"requirementId":"iwuic-2024-prescott-class-3-one-hour-eave","scopeKeys":["ignition-resistant-class-3"],"scopeSummary":"This local one-hour eave path applies only after the City assigns IR3 construction.","sourceSections":["506.6"]}],"requirementCrosswalk":[{"modelRequirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized Class 1 and 2 exterior-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott rewrites Section 505.2 but retains the normalized Class A tested-assembly atom for Classes 1 and 2.","sourceSections":["504.2","505.2"]},{"modelRequirementId":"iwuic-2024-class-1-2-multilayered-glazing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized multilayered-glazing atom.","sourceSections":["504.8","505.8"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-deck","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized noncombustible-appendage atom.","sourceSections":["504.7","505.7"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized noncombustible-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized noncombustible-wall atom.","sourceSections":["504.5","505.5"]},{"modelRequirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized solid-core-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-noncombustible-eave","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized Class 1 noncombustible-eave atom.","sourceSections":["503.2.1","504.3"]},{"modelRequirementId":"iwuic-2024-class-1-wall-base-protection","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized wall-base atom.","sourceSections":["504.5.1"]},{"modelRequirementId":"iwuic-2024-class-2-solid-eave-enclosure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized Class 2 solid-eave atom.","sourceSections":["505.3"]},{"modelRequirementId":"iwuic-2024-class-3-class-b-roof-assembly","disposition":"locally-modified","replacementRequirementIds":["iwuic-2024-prescott-class-3-class-a-roof-assembly"],"scopeSummary":"Prescott rewrites Section 506.2 and replaces the model Class 3 Class B minimum with a Class A tested roof assembly.","sourceSections":["506.2"]},{"modelRequirementId":"iwuic-2024-noncombustible-gutters","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized noncombustible gutter-and-downspout atom.","sourceSections":["504.4","505.4","506.4"]},{"modelRequirementId":"iwuic-2024-roof-profile-closure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's rewritten Class 2 and 3 roof sections retain the normalized roof-profile closure atom.","sourceSections":["504.2","505.2","506.2"]},{"modelRequirementId":"iwuic-2024-roof-valley-flashing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's enumerated amendments do not modify the normalized valley-flashing atom.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"modelRequirementId":"iwuic-2024-vent-mesh","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Prescott's rewritten Section 506.5 expressly points Class 3 vents to the Class 1 prescriptive or tested paths, retaining the normalized vent atom.","sourceSections":["504.10.2","505.10.2","506.5"]}],"map":{"status":"official-map-required-not-located","summary":"Section 302.1 declares the entire city WUI, but Sections 302.2 and 502 require the City's public GIS and predictive model to assign the parcel's risk severity; the exact current public risk-layer URL was not located.","source":{"title":"Prescott City Code 6-2, Sections 302.1, 302.2, and 502","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"}},"projectTriggers":[{"summary":"The code applies to construction, alteration, movement, repair, maintenance, and use of buildings, structures, or premises within Prescott's declared citywide WUI, subject to stated exceptions.","sourceSections":["101.2","302.1"],"source":{"title":"Prescott City Code 6-2","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"}},{"summary":"Additions or alterations that increase the existing footprint by 500 square feet or more must conform as new construction; separate Section 105.3 thresholds and Appendix B vegetation requirements remain part of the project review.","sourceSections":["101.5","105.3"],"source":{"title":"Prescott City Code 6-2","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"}},{"summary":"Chapter 5 exemptions include specified interior work, additions no larger than 500 square feet, work affecting less than 25 percent of stated exterior areas, listed accessory structures, and maintenance work; the code official determines the project result.","sourceSections":["105.3"],"source":{"title":"Prescott City Code 6-2","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"}}],"localAmendments":[{"kind":"modification","section":"6-2-1","summary":"Prescott adopts the 2024 International Wildland-Urban Interface Code by reference through Resolution 2026-1983 and records Ordinance 2026-1943 on May 12, 2026.","source":{"title":"Prescott City Code 6-2","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"}},{"kind":"modification","section":"302.1–302.2, 502, and 503.1","summary":"Prescott declares the entire city WUI and maps extreme risk to IR1, high risk to IR2, and moderate risk to IR3 through City predictive modeling and GIS.","source":{"title":"Prescott City Code 6-2","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"}},{"kind":"modification","section":"505.2 and 506.2","summary":"Prescott requires a Class A ASTM E108 or UL 790 roof assembly for both Class 2 and Class 3 construction and retains stated roof-profile closure alternatives.","source":{"title":"Prescott City Code 6-2","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"}},{"kind":"addition","section":"506.6","summary":"Prescott adds Class 3 eave, soffit, and fascia-back protection paths using ignition-resistant, one-hour, dimensional-lumber, or exterior fire-retardant-treated material alternatives.","source":{"title":"Prescott City Code 6-2","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"}}],"supportingSources":[{"title":"Prescott building permits and current code-adoption links","url":"https://prescott-az.gov/permit-center/permit-categories/building-permits/","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}],"unresolvedPredicates":["official-boundary","official-hazard-map","official-hazard-class","project-type","effective-date","official-confirmation"],"source":{"title":"Prescott City Code 6-2 Urban-Wildland Interface Code","url":"https://www.codepublishing.com/AZ/Prescott/html/Prescott06/Prescott062.html","publisher":"City of Prescott","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2026-05-12T00:00:00.000Z"},"author":"grayson-graham","reviewStatus":"draft","lastVerified":"2026-08-26T00:00:00.000Z"},{"id":"iwuic-2024-teton-county","title":"Unincorporated Teton County 2024 IWUIC application","instrumentId":"iwuic-2024","placeId":"us-wy-teton","status":"active","geographicScope":"unincorporated-county","scopeSummary":"Teton County applies its amended 2024 IWUIC only within unincorporated county lands; Fire/EMS separately determines whether IR construction applies and, if so, assigns IR3, IR2, or IR1 after its site-hazard review.","adoptedOn":"2025-01-07T00:00:00.000Z","effectiveOn":"2025-02-01T00:00:00.000Z","requirementIds":["iwuic-2024-class-1-2-20-minute-exterior-door","iwuic-2024-class-1-2-class-a-roof-assembly","iwuic-2024-class-1-2-multilayered-glazing","iwuic-2024-class-1-2-noncombustible-deck","iwuic-2024-class-1-2-noncombustible-exterior-door","iwuic-2024-class-1-2-noncombustible-exterior-wall","iwuic-2024-class-1-2-solid-core-exterior-door","iwuic-2024-class-1-noncombustible-eave","iwuic-2024-class-1-wall-base-protection","iwuic-2024-class-2-solid-eave-enclosure","iwuic-2024-class-3-class-b-roof-assembly","iwuic-2024-noncombustible-gutters","iwuic-2024-roof-profile-closure","iwuic-2024-roof-valley-flashing","iwuic-2024-vent-mesh"],"requirementCoverage":"complete","requirementCoverageSummary":"All 15 normalized model material rows were reviewed against the enacted local amendments; this is complete only for that model crosswalk, not full-code normalization or a finding that every class row applies to one project.","requirementScopes":[{"requirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This exterior-door path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This Class A roof path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.2","505.2"]},{"requirementId":"iwuic-2024-class-1-2-multilayered-glazing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This multilayered-glazing path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.8","505.8"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-deck","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible appendage path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.7","505.7"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-door path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-wall path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.5","505.5"]},{"requirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This solid-core exterior-door path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-noncombustible-eave","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This eave path applies only when Fire/EMS assigns IR1 construction.","sourceSections":["503.2.1","504.3"]},{"requirementId":"iwuic-2024-class-1-wall-base-protection","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This wall-base path applies only when Fire/EMS assigns IR1 construction.","sourceSections":["504.5.1"]},{"requirementId":"iwuic-2024-class-2-solid-eave-enclosure","scopeKeys":["ignition-resistant-class-2"],"scopeSummary":"This solid eave-enclosure path applies only when Fire/EMS assigns IR2 construction.","sourceSections":["505.3"]},{"requirementId":"iwuic-2024-class-3-class-b-roof-assembly","scopeKeys":["ignition-resistant-class-3"],"scopeSummary":"This Class B roof path applies only when Fire/EMS assigns IR3 construction.","sourceSections":["506.2"]},{"requirementId":"iwuic-2024-noncombustible-gutters","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This gutter-and-downspout path applies after Fire/EMS assigns IR1, IR2, or IR3 construction.","sourceSections":["504.4","505.4","506.4"]},{"requirementId":"iwuic-2024-roof-profile-closure","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This roof-profile closure applies after Fire/EMS assigns IR1, IR2, or IR3 construction.","sourceSections":["504.2","505.2","506.2"]},{"requirementId":"iwuic-2024-roof-valley-flashing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This valley-flashing path applies after Fire/EMS assigns IR1, IR2, or IR3 construction.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"requirementId":"iwuic-2024-vent-mesh","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This vent-mesh path applies after Fire/EMS assigns IR1, IR2, or IR3 construction.","sourceSections":["504.10.2","505.10.2","506.5"]}],"requirementCrosswalk":[{"modelRequirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized 20-minute exterior-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized Class A roof atom.","sourceSections":["504.2","505.2"]},{"modelRequirementId":"iwuic-2024-class-1-2-multilayered-glazing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized multilayered-glazing atom.","sourceSections":["504.8","505.8"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-deck","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-appendage atom.","sourceSections":["504.7","505.7"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-wall atom.","sourceSections":["504.5","505.5"]},{"modelRequirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized solid-core-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-noncombustible-eave","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-eave atom.","sourceSections":["503.2.1","504.3"]},{"modelRequirementId":"iwuic-2024-class-1-wall-base-protection","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized wall-base atom.","sourceSections":["504.5.1"]},{"modelRequirementId":"iwuic-2024-class-2-solid-eave-enclosure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized solid-eave atom.","sourceSections":["505.3"]},{"modelRequirementId":"iwuic-2024-class-3-class-b-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized Class B roof atom.","sourceSections":["506.2"]},{"modelRequirementId":"iwuic-2024-noncombustible-gutters","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-gutter atom.","sourceSections":["504.4","505.4","506.4"]},{"modelRequirementId":"iwuic-2024-roof-profile-closure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized roof-profile atom.","sourceSections":["504.2","505.2","506.2"]},{"modelRequirementId":"iwuic-2024-roof-valley-flashing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized valley-flashing atom.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"modelRequirementId":"iwuic-2024-vent-mesh","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized prescriptive vent-mesh atom.","sourceSections":["504.10.2","505.10.2","506.5"]}],"map":{"status":"linked-official-tool","summary":"Check the parcel/private-land status in the linked official WUI map; a ZIP does not establish inclusion, and Fire/EMS separately assigns the site-specific IR3, IR2, IR1, or does-not-apply result.","url":"https://gis.tetoncountywy.gov/portal/apps/experiencebuilder/experience/?id=0c66d130a6ee459fa3ea7f0a31d1e167","source":{"title":"Teton County WUI map","url":"https://gis.tetoncountywy.gov/portal/apps/experiencebuilder/experience/?id=0c66d130a6ee459fa3ea7f0a31d1e167","publisher":"Teton County, Wyoming","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},"projectTriggers":[{"summary":"Except for the stated exemptions, the Building Departments require the Fire/EMS WUI review and permit number before accepting a permit submittal.","sourceSections":["Submitting for IWUIC review"],"source":{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"A one-story detached tool shed, storage shed, playhouse, or similar accessory structure is exempt only when floor area does not exceed 120 square feet and it is more than 50 feet from the nearest adjacent structure.","sourceSections":["WUI review exemptions"],"source":{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"A strictly interior project is exempt only when it does not affect exterior components, including windows, doors, or decking; Fire/EMS separately states interior-only projects do not require a WUI permit.","sourceSections":["WUI review exemptions"],"source":{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"Re-roofing does not require a WUI permit under the current Fire/EMS guidance; applicants are told to contact Fire/EMS before submittal when project status is unclear.","sourceSections":["WUI review exemptions"],"source":{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"The local Section 101.5 exception requires additions or alterations of no more than 500 square feet to conform as new construction except for Section 602, subject to its sprinkler condition.","sourceSections":["101.5"],"source":{"title":"2024 Teton County Fire Code Resolution","url":"https://tetoncountywy.gov/DocumentCenter/View/32669/2024-Teton-County-Fire-Code-Resolution-Signed-Current","publisher":"Teton County, Wyoming","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-01-07T00:00:00.000Z"}}],"localAmendments":[{"kind":"exception","section":"101.5","summary":"The resolution adds a local rule for additions or alterations of no more than 500 square feet, with a Section 602 sprinkler exception.","source":{"title":"2024 Teton County Fire Code Resolution","url":"https://tetoncountywy.gov/DocumentCenter/View/32669/2024-Teton-County-Fire-Code-Resolution-Signed-Current","publisher":"Teton County, Wyoming","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-01-07T00:00:00.000Z"}},{"kind":"addition","section":"503.2.1.1","summary":"The resolution prohibits wood shake shingles or siding inside the mapped WUI.","source":{"title":"2024 Teton County Fire Code Resolution","url":"https://tetoncountywy.gov/DocumentCenter/View/32669/2024-Teton-County-Fire-Code-Resolution-Signed-Current","publisher":"Teton County, Wyoming","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-01-07T00:00:00.000Z"}},{"kind":"deletion","section":"503.2.3","summary":"The resolution strikes the model wood-roof-covering section while adding its separate local wood prohibition.","source":{"title":"2024 Teton County Fire Code Resolution","url":"https://tetoncountywy.gov/DocumentCenter/View/32669/2024-Teton-County-Fire-Code-Resolution-Signed-Current","publisher":"Teton County, Wyoming","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-01-07T00:00:00.000Z"}},{"kind":"exception","section":"504.10.3","summary":"The resolution allows cold-roof ventilation when vents meet Section 504.10.1 for all ignition-resistant construction types.","source":{"title":"2024 Teton County Fire Code Resolution","url":"https://tetoncountywy.gov/DocumentCenter/View/32669/2024-Teton-County-Fire-Code-Resolution-Signed-Current","publisher":"Teton County, Wyoming","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-01-07T00:00:00.000Z"}}],"supportingSources":[{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}],"unresolvedPredicates":["official-boundary","official-hazard-map","official-hazard-class","project-type","effective-date","official-confirmation"],"source":{"title":"2024 Teton County Fire Code Resolution","url":"https://tetoncountywy.gov/DocumentCenter/View/32669/2024-Teton-County-Fire-Code-Resolution-Signed-Current","publisher":"Teton County, Wyoming","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-01-07T00:00:00.000Z"},"author":"grayson-graham","reviewStatus":"draft","lastVerified":"2026-08-26T00:00:00.000Z"},{"id":"iwuic-2024-town-of-jackson","title":"Town of Jackson 2024 IWUIC application","instrumentId":"iwuic-2024","placeId":"us-wy-jackson","status":"active","geographicScope":"incorporated-boundary","scopeSummary":"The Town of Jackson declares its entire corporate boundary, including later amendments, within the WUI; Fire/EMS still determines whether IR construction applies and, if so, assigns IR3, IR2, or IR1 after its site-hazard review.","adoptedOn":"2024-12-16T00:00:00.000Z","effectiveOn":"2025-01-01T00:00:00.000Z","requirementIds":["iwuic-2024-class-1-2-20-minute-exterior-door","iwuic-2024-class-1-2-class-a-roof-assembly","iwuic-2024-class-1-2-multilayered-glazing","iwuic-2024-class-1-2-noncombustible-deck","iwuic-2024-class-1-2-noncombustible-exterior-door","iwuic-2024-class-1-2-noncombustible-exterior-wall","iwuic-2024-class-1-2-solid-core-exterior-door","iwuic-2024-class-1-noncombustible-eave","iwuic-2024-class-1-wall-base-protection","iwuic-2024-class-2-solid-eave-enclosure","iwuic-2024-class-3-class-b-roof-assembly","iwuic-2024-noncombustible-gutters","iwuic-2024-roof-profile-closure","iwuic-2024-roof-valley-flashing","iwuic-2024-vent-mesh"],"requirementCoverage":"complete","requirementCoverageSummary":"All 15 normalized model material rows were reviewed against the enacted local amendments; this is complete only for that model crosswalk, not full-code normalization or a finding that every class row applies to one project.","requirementScopes":[{"requirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This exterior-door path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This Class A roof path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.2","505.2"]},{"requirementId":"iwuic-2024-class-1-2-multilayered-glazing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This multilayered-glazing path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.8","505.8"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-deck","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible appendage path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.7","505.7"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-door path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-wall path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.5","505.5"]},{"requirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This solid-core exterior-door path applies only when Fire/EMS assigns IR1 or IR2 construction.","sourceSections":["504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-noncombustible-eave","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This eave path applies only when Fire/EMS assigns IR1 construction.","sourceSections":["503.2.1","504.3"]},{"requirementId":"iwuic-2024-class-1-wall-base-protection","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This wall-base path applies only when Fire/EMS assigns IR1 construction.","sourceSections":["504.5.1"]},{"requirementId":"iwuic-2024-class-2-solid-eave-enclosure","scopeKeys":["ignition-resistant-class-2"],"scopeSummary":"This solid eave-enclosure path applies only when Fire/EMS assigns IR2 construction.","sourceSections":["505.3"]},{"requirementId":"iwuic-2024-class-3-class-b-roof-assembly","scopeKeys":["ignition-resistant-class-3"],"scopeSummary":"This Class B roof path applies only when Fire/EMS assigns IR3 construction.","sourceSections":["506.2"]},{"requirementId":"iwuic-2024-noncombustible-gutters","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This gutter-and-downspout path applies after Fire/EMS assigns IR1, IR2, or IR3 construction.","sourceSections":["504.4","505.4","506.4"]},{"requirementId":"iwuic-2024-roof-profile-closure","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This roof-profile closure applies after Fire/EMS assigns IR1, IR2, or IR3 construction.","sourceSections":["504.2","505.2","506.2"]},{"requirementId":"iwuic-2024-roof-valley-flashing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This valley-flashing path applies after Fire/EMS assigns IR1, IR2, or IR3 construction.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"requirementId":"iwuic-2024-vent-mesh","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This vent-mesh path applies after Fire/EMS assigns IR1, IR2, or IR3 construction.","sourceSections":["504.10.2","505.10.2","506.5"]}],"requirementCrosswalk":[{"modelRequirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized 20-minute exterior-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized Class A roof atom.","sourceSections":["504.2","505.2"]},{"modelRequirementId":"iwuic-2024-class-1-2-multilayered-glazing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized multilayered-glazing atom.","sourceSections":["504.8","505.8"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-deck","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-appendage atom.","sourceSections":["504.7","505.7"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-wall atom.","sourceSections":["504.5","505.5"]},{"modelRequirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized solid-core-door atom.","sourceSections":["504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-noncombustible-eave","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-eave atom.","sourceSections":["503.2.1","504.3"]},{"modelRequirementId":"iwuic-2024-class-1-wall-base-protection","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized wall-base atom.","sourceSections":["504.5.1"]},{"modelRequirementId":"iwuic-2024-class-2-solid-eave-enclosure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized solid-eave atom.","sourceSections":["505.3"]},{"modelRequirementId":"iwuic-2024-class-3-class-b-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized Class B roof atom.","sourceSections":["506.2"]},{"modelRequirementId":"iwuic-2024-noncombustible-gutters","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized noncombustible-gutter atom.","sourceSections":["504.4","505.4","506.4"]},{"modelRequirementId":"iwuic-2024-roof-profile-closure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized roof-profile atom.","sourceSections":["504.2","505.2","506.2"]},{"modelRequirementId":"iwuic-2024-roof-valley-flashing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized valley-flashing atom.","sourceSections":["504.2.1","505.2.1","506.2.1"]},{"modelRequirementId":"iwuic-2024-vent-mesh","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"The local Chapter 5 amendments do not change the normalized prescriptive vent-mesh atom.","sourceSections":["504.10.2","505.10.2","506.5"]}],"map":{"status":"declared-authority-wide","summary":"Ordinance 1416 declares the entire current Town boundary within the WUI, but Fire/EMS still assigns the project-specific IR3, IR2, IR1, or does-not-apply result after site-hazard review.","source":{"title":"Town of Jackson Ordinance 1416, Section F","url":"https://www.tetoncountywy.gov/DocumentCenter/View/32222/TOJ-2024-Fire-Code-Current","publisher":"Town of Jackson","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2024-12-16T00:00:00.000Z"}},"projectTriggers":[{"summary":"Except for the stated exemptions, the Building Departments require the Fire/EMS WUI review and permit number before accepting a permit submittal.","sourceSections":["Submitting for IWUIC review"],"source":{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"A one-story detached tool shed, storage shed, playhouse, or similar accessory structure is exempt only when floor area does not exceed 120 square feet and it is more than 50 feet from the nearest adjacent structure.","sourceSections":["WUI review exemptions"],"source":{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"A strictly interior project is exempt only when it does not affect exterior components, including windows, doors, or decking; Fire/EMS separately states interior-only projects do not require a WUI permit.","sourceSections":["WUI review exemptions"],"source":{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"Re-roofing does not require a WUI permit under the current Fire/EMS guidance; applicants are told to contact Fire/EMS before submittal when project status is unclear.","sourceSections":["WUI review exemptions"],"source":{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"The local Section 101.5 exception requires additions or alterations of no more than 500 square feet to conform as new construction except for Section 602, subject to its sprinkler condition.","sourceSections":["101.5"],"source":{"title":"Town of Jackson Ordinance 1416","url":"https://www.tetoncountywy.gov/DocumentCenter/View/32222/TOJ-2024-Fire-Code-Current","publisher":"Town of Jackson","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2024-12-16T00:00:00.000Z"}}],"localAmendments":[{"kind":"exception","section":"101.5","summary":"Ordinance 1416 adds a local rule for additions or alterations of no more than 500 square feet, with a Section 602 sprinkler exception.","source":{"title":"Town of Jackson Ordinance 1416","url":"https://www.tetoncountywy.gov/DocumentCenter/View/32222/TOJ-2024-Fire-Code-Current","publisher":"Town of Jackson","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2024-12-16T00:00:00.000Z"}},{"kind":"addition","section":"503.2.1.1","summary":"Ordinance 1416 prohibits wood shake, wood shingles, or siding inside the WUI.","source":{"title":"Town of Jackson Ordinance 1416","url":"https://www.tetoncountywy.gov/DocumentCenter/View/32222/TOJ-2024-Fire-Code-Current","publisher":"Town of Jackson","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2024-12-16T00:00:00.000Z"}},{"kind":"deletion","section":"503.2.3","summary":"Ordinance 1416 strikes the model wood-roof-covering section while adding its separate local wood prohibition.","source":{"title":"Town of Jackson Ordinance 1416","url":"https://www.tetoncountywy.gov/DocumentCenter/View/32222/TOJ-2024-Fire-Code-Current","publisher":"Town of Jackson","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2024-12-16T00:00:00.000Z"}},{"kind":"exception","section":"504.10.3","summary":"Ordinance 1416 allows cold-roof ventilation when vents meet Section 504.10.1 for all ignition-resistant construction types.","source":{"title":"Town of Jackson Ordinance 1416","url":"https://www.tetoncountywy.gov/DocumentCenter/View/32222/TOJ-2024-Fire-Code-Current","publisher":"Town of Jackson","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2024-12-16T00:00:00.000Z"}}],"supportingSources":[{"title":"WUI Information for Contractors","url":"https://www.tetoncountywy.gov/671/WUI-Information-for-Contractors","publisher":"Jackson Hole Fire/EMS","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}],"unresolvedPredicates":["official-boundary","official-hazard-class","project-type","effective-date","official-confirmation"],"source":{"title":"Town of Jackson Ordinance 1416","url":"https://www.tetoncountywy.gov/DocumentCenter/View/32222/TOJ-2024-Fire-Code-Current","publisher":"Town of Jackson","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2024-12-16T00:00:00.000Z"},"author":"grayson-graham","reviewStatus":"draft","lastVerified":"2026-08-26T00:00:00.000Z"},{"id":"iwuic-2024-washoe-county","title":"Washoe County 2024 IWUIC Chapter 5 application","instrumentId":"iwuic-2024","placeId":"us-nv-washoe","status":"active","geographicScope":"unincorporated-county","scopeSummary":"Washoe County's Building Program applies 2024 IWUIC Chapter 5 under Ordinance 1736, while the companion Chapter 60 fire-code adoption supplies the fire-authority inputs in Truckee Meadows Fire Protection District and other unincorporated areas where the County has fire responsibility; boundary, parcel hazard, water, defensible space, assigned IR class, project, transition date, and official checks remain open.","adoptedOn":"2025-06-10T00:00:00.000Z","effectiveOn":"2025-07-01T00:00:00.000Z","requirementIds":["iwuic-2024-class-1-2-20-minute-exterior-door","iwuic-2024-class-1-2-class-a-roof-assembly","iwuic-2024-class-1-2-multilayered-glazing","iwuic-2024-class-1-2-noncombustible-deck","iwuic-2024-class-1-2-noncombustible-exterior-door","iwuic-2024-class-1-2-noncombustible-exterior-wall","iwuic-2024-class-1-2-solid-core-exterior-door","iwuic-2024-class-1-noncombustible-eave","iwuic-2024-class-1-wall-base-protection","iwuic-2024-class-2-solid-eave-enclosure","iwuic-2024-class-3-class-b-roof-assembly","iwuic-2024-noncombustible-gutters","iwuic-2024-roof-profile-closure","iwuic-2024-roof-valley-flashing","iwuic-2024-vent-mesh"],"requirementCoverage":"complete","requirementCoverageSummary":"All 15 normalized model material rows were reviewed against Washoe County's Chapter 5 adoption and current official construction guide; this is complete only for that model crosswalk, not full-code normalization or a finding that every class row applies to one project.","requirementScopes":[{"requirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This exterior-door path applies only after the County and fire district inputs route the project to IR1 or IR2 construction.","sourceSections":["503.1","504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This Class A roof path applies only after the County and fire district inputs route the project to IR1 or IR2 construction.","sourceSections":["503.1","504.2","505.2"]},{"requirementId":"iwuic-2024-class-1-2-multilayered-glazing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This multilayered-glazing path applies only after the County and fire district inputs route the project to IR1 or IR2 construction.","sourceSections":["503.1","504.8","505.8"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-deck","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible appendage path applies only after the County and fire district inputs route the project to IR1 or IR2 construction.","sourceSections":["503.1","504.7","505.7"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-door path applies only after the County and fire district inputs route the project to IR1 or IR2 construction.","sourceSections":["503.1","504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This noncombustible exterior-wall path applies only after the County and fire district inputs route the project to IR1 or IR2 construction.","sourceSections":["503.1","504.5","505.5"]},{"requirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2"],"scopeSummary":"This solid-core exterior-door path applies only after the County and fire district inputs route the project to IR1 or IR2 construction.","sourceSections":["503.1","504.9","505.9"]},{"requirementId":"iwuic-2024-class-1-noncombustible-eave","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This eave path applies only after the County and fire district inputs route the project to IR1 construction.","sourceSections":["503.1","503.2.1","504.3"]},{"requirementId":"iwuic-2024-class-1-wall-base-protection","scopeKeys":["ignition-resistant-class-1"],"scopeSummary":"This wall-base path applies only after the County and fire district inputs route the project to IR1 construction.","sourceSections":["503.1","504.5.1"]},{"requirementId":"iwuic-2024-class-2-solid-eave-enclosure","scopeKeys":["ignition-resistant-class-2"],"scopeSummary":"This solid eave-enclosure path applies only after the County and fire district inputs route the project to IR2 construction.","sourceSections":["503.1","505.3"]},{"requirementId":"iwuic-2024-class-3-class-b-roof-assembly","scopeKeys":["ignition-resistant-class-3"],"scopeSummary":"This Class B roof path applies only after the County and fire district inputs route the project to IR3 construction.","sourceSections":["503.1","506.2"]},{"requirementId":"iwuic-2024-noncombustible-gutters","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This gutter-and-downspout path applies after the County and fire district inputs route the project to IR1, IR2, or IR3 construction.","sourceSections":["503.1","504.4","505.4","506.4"]},{"requirementId":"iwuic-2024-roof-profile-closure","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This roof-profile closure applies after the County and fire district inputs route the project to IR1, IR2, or IR3 construction.","sourceSections":["503.1","504.2","505.2","506.2"]},{"requirementId":"iwuic-2024-roof-valley-flashing","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This valley-flashing path applies after the County and fire district inputs route the project to IR1, IR2, or IR3 construction.","sourceSections":["503.1","504.2.1","505.2.1","506.2.1"]},{"requirementId":"iwuic-2024-vent-mesh","scopeKeys":["ignition-resistant-class-1","ignition-resistant-class-2","ignition-resistant-class-3"],"scopeSummary":"This vent-mesh path applies after the County and fire district inputs route the project to IR1, IR2, or IR3 construction.","sourceSections":["503.1","504.10.2","505.10.2","506.5"]}],"requirementCrosswalk":[{"modelRequirementId":"iwuic-2024-class-1-2-20-minute-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model exterior-door atom.","sourceSections":["Chapter 5","504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-class-a-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model Class A roof atom.","sourceSections":["Chapter 5","504.2","505.2"]},{"modelRequirementId":"iwuic-2024-class-1-2-multilayered-glazing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model multilayered-glazing atom.","sourceSections":["Chapter 5","504.8","505.8"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-deck","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model noncombustible-appendage atom.","sourceSections":["Chapter 5","504.7","505.7"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model noncombustible-door atom.","sourceSections":["Chapter 5","504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-2-noncombustible-exterior-wall","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model noncombustible-wall atom.","sourceSections":["Chapter 5","504.5","505.5"]},{"modelRequirementId":"iwuic-2024-class-1-2-solid-core-exterior-door","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model solid-core-door atom.","sourceSections":["Chapter 5","504.9","505.9"]},{"modelRequirementId":"iwuic-2024-class-1-noncombustible-eave","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model noncombustible-eave atom.","sourceSections":["Chapter 5","503.2.1","504.3"]},{"modelRequirementId":"iwuic-2024-class-1-wall-base-protection","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model wall-base atom.","sourceSections":["Chapter 5","504.5.1"]},{"modelRequirementId":"iwuic-2024-class-2-solid-eave-enclosure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model solid eave-enclosure atom.","sourceSections":["Chapter 5","505.3"]},{"modelRequirementId":"iwuic-2024-class-3-class-b-roof-assembly","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model Class B roof atom.","sourceSections":["Chapter 5","506.2"]},{"modelRequirementId":"iwuic-2024-noncombustible-gutters","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model noncombustible-gutter atom.","sourceSections":["Chapter 5","504.4","505.4","506.4"]},{"modelRequirementId":"iwuic-2024-roof-profile-closure","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model roof-profile atom.","sourceSections":["Chapter 5","504.2","505.2","506.2"]},{"modelRequirementId":"iwuic-2024-roof-valley-flashing","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model valley-flashing atom.","sourceSections":["Chapter 5","504.2.1","505.2.1","506.2.1"]},{"modelRequirementId":"iwuic-2024-vent-mesh","disposition":"adopted-unchanged","replacementRequirementIds":[],"scopeSummary":"Washoe's Chapter 5 adoption and current guide retain the model prescriptive vent-mesh atom.","sourceSections":["Chapter 5","504.10.2","505.10.2","506.5"]}],"map":{"status":"linked-official-tool","summary":"Washoe's official EZ Fire-WUI map accepts an address or APN and returns the parcel hazard category; the applicable fire district must separately confirm water and defensible-space conformity before Table 503.1 yields an IR class.","url":"https://gis.washoecounty.us/wrms/quick/firehazard?auth=0","source":{"title":"Washoe County Wildland Urban Interface Code Guide","url":"https://www.washoecounty.gov/building/Informational_Pages/Wildland_Urban_Interface_Code_Guide.php","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},"projectTriggers":[{"summary":"Ordinance 1750 applies the companion fire-code layer within Truckee Meadows Fire Protection District and other unincorporated areas where Washoe County has fire responsibility; it adopts IWUIC Chapters 1 through 4, 6, and 7 for that layer, while building-construction matters and the separately adopted Chapter 5 remain with the building code official.","sourceSections":["60.100.010","60.100.020","Chapter 5 deletion","Section 202 Code Official"],"source":{"title":"Washoe County Ordinance 1750","url":"https://library.municode.com/nv/washoe_county/ordinances/code_of_ordinances?nodeId=1417368","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-12-16T00:00:00.000Z"}},{"summary":"The official guide routes construction through Table 503.1 only after the parcel hazard category and the applicable fire district's water and defensible-space conformity determinations are known.","sourceSections":["Fire Hazard Severity","Defensible Space and Water Conformity","Table 503.1"],"source":{"title":"Washoe County Wildland Urban Interface Code Guide","url":"https://www.washoecounty.gov/building/Informational_Pages/Wildland_Urban_Interface_Code_Guide.php","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}},{"summary":"For a building that predates this code, replacing at least 25 percent of the roof covering in a 12-month period routes the replacement covering to the new-construction requirement for the assigned ignition-resistant class.","sourceSections":["507.1"],"source":{"title":"Washoe County Wildland Urban Interface Code Guide","url":"https://www.washoecounty.gov/building/Informational_Pages/Wildland_Urban_Interface_Code_Guide.php","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}}],"localAmendments":[{"kind":"deletion","section":"Chapter 60 companion IWUIC, Chapter 5","summary":"Ordinance 1750 deletes Chapter 5 from the separate fire-code adoption that supplies Chapters 1 through 4, 6, and 7; that deletion does not erase Ordinance 1736's Chapter 100 building-code adoption of 2024 IWUIC Chapter 5.","source":{"title":"Washoe County Ordinance 1750","url":"https://library.municode.com/nv/washoe_county/ordinances/code_of_ordinances?nodeId=1417368","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-12-16T00:00:00.000Z"}},{"kind":"transition","section":"2024 code transition notice","summary":"Washoe County's adopted-code notice gives a July 1, 2025 effective date and a six-month transition; 2024 editions are required for submittals on and after January 1, 2026, while earlier 2018-code submittals remain under their submitted edition.","source":{"title":"Washoe County Adopted Building Codes","url":"https://www.washoecounty.gov/building/getting_started/building_codes.php","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}}],"supportingSources":[{"title":"Washoe County Ordinance 1750","url":"https://library.municode.com/nv/washoe_county/ordinances/code_of_ordinances?nodeId=1417368","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-12-16T00:00:00.000Z"},{"title":"History of Adopted Building Codes within Washoe County","url":"https://www.washoecounty.gov/building/Informational_Pages/History_of_Adopted_Building_Codes.php","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z","documentDate":"2025-06-10T00:00:00.000Z"},{"title":"Washoe County Wildland Urban Interface Code Guide","url":"https://www.washoecounty.gov/building/Informational_Pages/Wildland_Urban_Interface_Code_Guide.php","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"},{"title":"Washoe County EZ Fire-WUI Map","url":"https://gis.washoecounty.us/wrms/quick/firehazard?auth=0","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"}],"unresolvedPredicates":["official-boundary","official-hazard-map","official-hazard-class","project-type","effective-date","official-confirmation"],"source":{"title":"Washoe County Adopted Building Codes","url":"https://www.washoecounty.gov/building/getting_started/building_codes.php","publisher":"Washoe County","sourceType":"official","accessedOn":"2026-08-26T00:00:00.000Z"},"author":"grayson-graham","reviewStatus":"draft","lastVerified":"2026-08-26T00:00:00.000Z"}],"products":[{"id":"westlake-royal-ribbed-valley-metal","name":"Westlake Royal ribbed valley metal","url":"/materials/westlake-royal-ribbed-valley-metal/","categories":["roofing"],"complianceStatus":"attribute-match","documentedAttributes":[{"attribute":"assemblyRole","value":"valley-flashing","source":{"title":"Ribbed valley metal","url":"https://www.westlakeroyalbuildingproducts.com/roofing/westlake-royal-roofing-components/ribbed-valley-metal","publisher":"Westlake Royal Roofing LLC","accessedOn":"2026-08-24T00:00:00.000Z","sourceType":"manufacturer"},"documentLocation":null,"excerpt":null},{"attribute":"material","value":"galvanized-steel","source":{"title":"Ribbed valley metal","url":"https://www.westlakeroyalbuildingproducts.com/roofing/westlake-royal-roofing-components/ribbed-valley-metal","publisher":"Westlake Royal Roofing LLC","accessedOn":"2026-08-24T00:00:00.000Z","sourceType":"manufacturer"},"documentLocation":null,"excerpt":null},{"attribute":"sheetGauge","value":26,"source":{"title":"Ribbed valley metal","url":"https://www.westlakeroyalbuildingproducts.com/roofing/westlake-royal-roofing-components/ribbed-valley-metal","publisher":"Westlake Royal Roofing LLC","accessedOn":"2026-08-24T00:00:00.000Z","sourceType":"manufacturer"},"documentLocation":null,"excerpt":null},{"attribute":"corrosionResistant","value":true,"source":{"title":"Ribbed valley metal","url":"https://www.westlakeroyalbuildingproducts.com/roofing/westlake-royal-roofing-components/ribbed-valley-metal","publisher":"Westlake Royal Roofing LLC","accessedOn":"2026-08-24T00:00:00.000Z","sourceType":"manufacturer"},"documentLocation":null,"excerpt":null}]}],"matchContract":"Products appear only when their cited fields satisfy this requirement's normalized constraints. Application scope and unresolved predicates remain separate; an attribute match is not a permit decision."}